If you’re dealing with aviation systems measuring key power quality parameters at 400Hz is a must. The Fluke 437-II provides that capability (and measures at 50 and 60Hz too) and is designed for users who need to quickly get to the source of the power quality problem, so they can minimize expensive downtime.

The integrated shipboard power measurement system analyzes according to MIL-STD 1399 to automatically give a full evaluation of voltage, current and power according to the standard. This evaluation makes measurement and analysis as easy as can be. The measurement process and the way the 437-II displays data have been optimized to provide to the most important information as quickly as possible.

Specifications: Fluke 437 Series II 400 Hz Power Quality Monitor and Energy Analyzer

Product Specifications
Volt Model Measurement Range Resolution Accuracy
Vrms (ac+dc) 1 V to 1000 V phase to neutral 0.01 V ± 0.1% of nominal voltage**** 
Vpk 1 Vpk to 1400 Vpk 1 V 5% of nominal voltage
Voltage Crest Factor (CF) 1.0 > 2.8 0.01 ± 5 %
Vfund   0.1 V ± 0.1% of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (ac+dc) i430-Flex 1x  5 A to 6000 A 1 A ± 0.5% ± 5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ± 0.5% ± 5 counts
1mV/A 1x 5 A to 2000 A 1A ± 0.5% ± 5 counts
1mV/A 10x 0.5 A A to 200 A (ac only) 0.1 A ± 0.5% ± 5 counts
Apk i430-Flex  8400 Apk  1 Arms ± 5 %
1mV/A 5500 Apk 1 Arms ± 5 %
A Crest Factor (CF) 1 to 10 0.01 ± 5 %
Amps½ i430-Flex 1x  5 A to 6000 A  1 A  ± 1% ± 10 counts 
i430-Flex 10x 0.5 A to 600 A 0.1 A  ± 1% ± 10 counts
1mV/A 1x   5 A to 2000 A  1A  ± 1% ± 10 counts
1mV/A 10x 0.5 A A to 200 A (ac only) 0.1 A ± 1% ± 10 counts
Afund i430-Flex 1x  5 A to 6000 A 1 A ± 0.5% ± 5 counts 
i430-Flex 10x  0.5 A to 600 A 0.1 A ± 0.5% ± 5 counts
1mV/A 1x  5 A to 2000 A 1A ± 0.5% ± 5 counts
1mV/A 10x  0.5 A A to 200 A (ac only) 0.1 A ± 0.5% ± 5 counts
Hz
Fluke 437 @ 50 Hz nominal 42.500 Hz to 57.500 Hz 0.001 Hz ± 0.01 Hz
Fluke 437 @ 60 Hz nominal  51.000 Hz to 69.000 Hz 0.001 Hz ± 0.01 Hz
Fluke 437 @ 400 Hz nominal 340.0 Hz to 460.0 Hz 0.1 Hz ± 0.1 Hz
Power
Watts (VA, var) i430-Flex  max 6000 MW 0.1 W to 1 MW ± 1% ± 10 counts
1 mV/A max 2000 MW 0.1 W to 1 MW ± 1% ± 10 counts
Power Factor (Cos j/DPF) 0 to 1 0.001 ± 0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal ± 1% ± 10 counts
Energy Loss i430-Flex 10x Depends on clamp scaling and V nominal ± 1% ± 10 counts Excluding line resistance accuracy
Harmonics
Harmonic Order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-Harmonic Order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts % f 0.0 % to 100 % 0.1 % ± 0.1% ± n x 0.1 %
r 0.0 % to 100 % 0.1 % ± 0.1% ± n x 0.4 %
Absolute 0.0 to 1000 V 0.1 V ± 5% *
THD 0.0 % to 100 % 0.1 % ± 2.5 %
Amps % f 0.0 % to 100 % 0.1 % ± 0.1% ± n x 0.1%
r 0.0 % to 100 % 0.1 % ± 0.1% ± n x 0.4 %
Absolute 0.0 to 600 A 0.1 A ± 5% ± 5 counts
THD 0.0 % to 100 % 0.1 % ± 2.5 %
Watts % f or r  0.0 % to 100 % 0.1 % ± n x 2%
Absolute Depends on clamp scaling and V nominal  ± 5% ± n x 2 % ± 10 counts
THD 0.0 % to 100 %   0.1 % ± 5 %
Phase Angle  -360° to +0° ± n x 1°
Flicker
Plt, Pst, Pst (1min) Pinst 0.00 to 20.00 0.01 ± 5 %
Unbalance
Volts % 0.0 % to 20.0 % 0.1 % ± 0.1 %
Amps % 0.0 % to 20.0 % 0.1% ± 1 %
Mains Signaling
Threshold Levels Threshold, limits and signaling duration is programable for two signaling frequencies
Signaling Frequency 60 Hz to 3000 Hz 0.1 Hz  
Relative V% 0 % to 100 % 0.10 % ± 0.4 %
Absolute V3s (3 second avg.) 0.0 V to 1000 V 0.1 V ± 5 % of nominal voltage
General Specifications
Case Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory 16GB Wi-Fi SD card for standard models or 8GB SD card for /INTL models (SDHC compliant, FAT32 formatted), up to 32GB optionally. Screen save and multiple data memories for storing data including recordings (dependent on memory size).
Real-Time Clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture
Environmental
Operating Temperature 0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery
Storage Temperature -20 °C ~ +60 °C
Humidity +10 °C ~ +30 °C: 95% RH non-condensing
+30 °C ~ +40 °C: 75% RH non-condensing
+40 °C ~ +50 °C: 45% RH non-condensing
Maximum Operating Altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC) EN 61326 (2005-12) for emission and immunity
Interfaces Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
Warranty Three years (parts and labor) on main instrument, one year on accessories
View full family specifications »
*  ± 5 % if ≥ 1 % of nominal voltage ± 0.05 % of nominal voltage if < 1% of nominal voltage
**  50Hz/60Hz nominal frequency according to IEC 61000-4-30
***  400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode
****  For nominal voltage 50 V to 500 V

Key features: Fluke 437 Series II 400 Hz Power Quality Monitor and Energy Analyzer

The Fluke 437-II series helps you locate, predict, prevent and troubleshoot Power Quality Issues – 50Hz, 60Hz and 400Hz

  • 400 Hz operation for use in avionic and military applications
  • Shipboard power measurement system analyzes according to MIL-STD 1399 to automatically give a full evaluation of voltage, current and power
  • Advanced Power Quality Health— At-a-glance power quality health data in real-time so you have the data you need when you need it
Leave a review

Reviews

No reviews

Trending Items

Fluke Ti400 Thermal scanning Camera

Fluke Ti400 Thermal scanning Camera

Good
Fluke 115 True-RMS Digital Multimeter

Fluke 115 True-RMS Digital Multimeter

Good
Fluke 376 True RMS AC/DC Clamp Meter

Fluke 376 True RMS AC/DC Clamp Meter

Good
Fluke TiS20+ MAX Thermal Scanner

Fluke TiS20+ MAX Thermal Scanner

Good

You May Like Also

Amprobe AMB-50 Industrial High-Voltage Insulation Tester

Amprobe AMB-50 Industrial High-Voltage Insulation Tester

Good
Amprobe DGC-1000A Clamp Ground Resistance Tester

Amprobe DGC-1000A Clamp Ground Resistance Tester

Good
Fluke 437 Series II 400 Hz Power Quality Monitor and Energy Analyzer

Fluke 437 Series II 400 Hz Power Quality Monitor and Energy Analyzer

Good
Amprobe AMB-45 Insulation Resistance Tester

Amprobe AMB-45 Insulation Resistance Tester

Good